Electrical
Tests -
Electrical
testing of portable equipment will usually involve the following:-
- Earth
Bond Testing
- Insulation
Tests
Other
tests which may be carried out include:-
- Load
Testing
- Earth
Leakage Test
- Polarity
and Fuse checks
- Flash
Testing
|
|
|
Earth
Bond Test (Class 1 equipment only)
In order to
test that the earth bond is sound, a current of at least 1.5 times
the plug fuse rating is passed through the earth bond circuit for
a period of approximately 5 seconds.
Readings should
show less than 0.1+R Ohms (where R is the resistance of the lead)
If there is
a risk that the high current described above might cause damage,
an alternative test may be carried out using a low current of between
20mA and 200mA (usually a current of 100mA is used.)
Insulation
Resistance Test
The applied
test voltage should be approximately 500 Vdc
- Class 1
heating equipment < 3kW, 0.3M Ohms
- Class 1
All other equipment 1M Ohms
- Class 2
Equipment 2M Ohms
- Class 3
Equipment 250k Ohms
Optional
Tests
Flash
Test: No flashover or breakdown shall occur
Operation/Load
test: Compare reading with stated details on nameplate
Earth
leakage test:
Class 1 Handheld Appliances 0.75mA
Other Class 1 Appliances 3.5mA
Class 2 Appliances 0.25mA
Note that the
Earth Leakage Test is now normally referred to as the Touch Current
Test. Some testers offer a Substitue Leakage or Substitute Touch
Current Test which aims to carry out the same test but with reduced
voltage.
For information about 17th-edition testing and installation, visit our all new FREE information web site 17th-edition-regulations.info
This site is
provided to give FREE information on Pat Testing. The site is owned
and maintained by t2technical - the uk's leading pat testing specialists!
|